Glass Partition Building Regulations: Safety Glass, Manifestation, Fire and Access
The UK Building Regulations that apply to internal glass partitions: safety glazing, Approved Document K manifestation, fire safety under Part B and access under Part M.

Key takeaways
- Glass in critical locations must be safety glass that meets BS EN 12600.
- Large glass panels need manifestation at two heights under Approved Document K.
- Partitions on escape routes or compartment lines need tested fire-rated glazing.
- Doors must meet Part M access requirements for width and visibility.
Which regulations apply to glass partitions
In England, internal glazing is covered mainly by three parts of the Building Regulations, each with an Approved Document that explains how to comply. Wales, Scotland and Northern Ireland have their own equivalents, which are broadly similar.
This guide is a summary, not a substitute for the regulations or advice from your building control body. For how we deliver compliant systems, see our glass partition walls hub.
| Regulation | What it covers | What it means for glass partitions |
|---|---|---|
| Approved Document K | Protection from falling, collision and impact | Safety glass in critical locations; manifestation on large panels |
| Approved Document B | Fire safety | Fire-rated glazing on escape routes and compartment walls |
| Approved Document M | Access to and use of buildings | Door widths, visibility and contrast for disabled users |
Safety glass in critical locations
Glass in doors and side panels near doors, and glass in walls and partitions below a certain height, is classed as a critical location. Glass in these areas must either break safely or resist impact. In practice, almost every glass partition uses safety glass throughout.
Safety glass is classified by impact testing to BS EN 12600. Toughened and laminated glass are both used. The difference is explained in toughened vs laminated glass.
Manifestation
Large areas of clear glass that people could walk into must be marked so they are visible. Approved Document K sets out two zones for manifestation: one at around 850 to 1000 mm above floor level, and one at around 1400 to 1600 mm. Markings must contrast with the background behind them.
Manifestation can be plain bands, dots, frosted strips or branded graphics. See the glass manifestation guide for design options.
Fire safety
Where a partition forms part of an escape corridor, a protected stair, or a wall between fire compartments, it must keep its fire performance for the required time. This needs a tested fire-rated glazing system: the glass, frame, seals and fixings all tested together.
Fire ratings are expressed as integrity (E) or integrity and insulation (EI), with a time in minutes. Fire-rated glass partitioning explains the ratings in detail.
Access and doors
Part M sets out minimum clear opening widths for doors and requires doors and glazed screens to be visible to people with impaired sight. Contrasting door frames, handles and manifestation all help. Door closers must not make doors too heavy to open.
- Clear door opening widths suited to wheelchair users
- Visual contrast between doors, frames and the surrounding glass
- Manageable opening forces on closers
- Vision panels so people can see someone on the other side
Who signs off compliance
On commercial fit-outs, compliance is usually checked by an approved inspector or local authority building control, often as part of a wider fit-out application. We provide glass certification, fire test evidence and product data for the systems we install.
Official sources
The requirements summarised in this guide come from a small number of official documents. If you need to check the detail, these are the primary sources:
- The Building Regulations 2010 (opens in a new tab) on legislation.gov.uk.
- Approved Document K: protection from falling, collision and impact (opens in a new tab), covering safety glazing in critical locations and manifestation.
- Approved Document B: fire safety (opens in a new tab), covering fire-resisting construction.
- Approved Document M: access to and use of buildings (opens in a new tab), covering accessible doors and visibility.
- The Workplace (Health, Safety and Welfare) Regulations 1992 (opens in a new tab), including Regulation 14 on transparent doors and partitions.
Questions
Do all glass partitions need safety glass?
In practice, yes. Most partition glass falls within critical locations, so safety glass to BS EN 12600 is used throughout.
At what height should manifestation go?
Approved Document K suggests two zones: around 850 to 1000 mm and around 1400 to 1600 mm above floor level.
Do you provide certification?
Yes. We supply glass stamps or certificates and fire test evidence for the systems we install, for your building control file.